| ATEX Products |
 |
| Des têtes bien faites... |
|
|
|
| BAMOPHOX 322, RESISTIVITY / CONDUCTIVITY |
General Catalogue 322-01 |
BAMOPHOX 322, RESISTIVITY / CONDUCTIVITY
- µS or MΩ built-in program
- Programmable scales: 0 - 200 Ω up to 0 - 200 MΩ 0 - 2 µS up to 0 - 20 mS TOR version: 0 - 2 mS up to 0 - 2000 mS
- Convenient probesfactor: 10 - 1 - 0.1 - 0.01 TOR sensor TCS 100
- Temperature compensation Automatic or manual
- 2 analog outputs 0/4-20mA, galvanic insulated - 3 relay outputs (Normally open contact) - 1 input to switch the regulation on Stand-by
- 2 models: Panel mounting 72 x 144 (322E) Wall mounting IP 65 (322M)
- OPTIONS : RS 422 /J-BUS + LOGGER Extension for 2nd measurement input
|
An extension terminal (wall or panel mounting):
-Allows a second measurement parameter (pH, Conductivity, Chlorine,Turbidity, Flow, and 4-20 mA, depending of the model)
- The data from this blind device are displayed on the main device (second line display). A 4 wires shielded cable is necessary to link both devices (maximum length of 500m)
- The options RS422 and the data logger are shared between bothBAMOPHOX. |
The BAMOPHOX 322 offers high flexibility on use mixing different built-inprogrammes for regulation, thresholds, temperature compensation, andalarms. The 2 lines back lighted display, 16 alphanumerical characters,gives an easy measurement and temperature reading in any conditions. Italso displays the configuration menu and settings of thresholds, analogicaloutputs, operation data modes, calibration steps. To allow a quick and easy diagnostic after configuration a simulation program is built-in with direct actuation on contacts outputs,analogical outputs and PID regulation. A copy of the signal on the 4-20 mA output is galvanic insulated; it can be set up within theall range of the parameter. Temperature measurement is also available on a 4-20 mA output (this output is not available when PIDregulation is in use). Associated probes may have a conductance factor from 0,01 to 10 to get an accurate measurement from 200 ?up to 200 M?or from 2 ?S up to 20 mS. |
Displayed parameters: Measurement values - Configuration Menu - Temperature value
Display: Back lighted - 2 lines of 16 alphanumerical characters ; 9,2 mm high
Indication: LED alarms status
Configuration: 8 push buttons keyboard on front face - Keyword protected
Scales: 322 CE 0...2 µS, 0...20 µS, 0...200 µS, 0...2 mS, 0...20 mS 322 RE 0...200 Ω, 0...2 kΩ, 0...20 kΩ, 0...200 kΩ, 0...2 MΩ, 0...20 MΩ, 0...200 MΩ 322 TOR 0...20 mS, 0...200 mS, 0...2000 mS
Accuracy: ±0,3%, ±0,3°C
Probe input: BNC plug
Temperature compensation: Automatic with an input for a 3 wires Pt 100 Ohm/0°C, range 0…100°C Manually from 0…100°C
Relay outputs: 4 closing contacts (Silver alloy), voltage free Thresholds: 3 programmable independent thresholds - with adjustable hysteresis 0…100% and adjustable timer from 0 to 9999 sec Output relay: Common alarm signal for system dysfunction: Contact: Initial resistance 100 mΩ as a maximum (voltage drop 6 V DC 1 A) Rated at 831 V AC / 3 A / 277 V AC ; 90 W / 3 A / 30 V DC Switching capacity (minimum) 100 mA, 5 V DC (depending of switching frequency,ambient conditions, accuracy) Mechanical life time (minimum) 5 x106operations (180 commutation/min) Electrical life time (minimum) 2 x105 (20 comm./min) [3 A, 125 V AC], [3 A, 30 V DC]and 105(evaluated charge) for 3 A, 125 V AC
Measurement output: 0/4-20 mA (maxi 600 ?) proportional to measurement, galvanic insulated
Temperature output: 0/4-20 mA (max 600 ?), scaling 0…100°C, galvanic insulated
Program Testing: Simulation through the menu on measurement, temperature, and relay outputs
Main power supply: 230 V AC / 50-60 Hz [other on request] - Consumption 10 VA
Models: Panel mounting, IP65, 72 x 144 mm, connections on screw terminal IP40 Cycle average measurement record, with a programmable period,150000 records maxi on MMC (multi media card) / External driver necessary
OPTION (RS 422 + Logger) Communication: RS422 output, J-BUS link, binary slave mode, 2400 to 9600 bauds Data Logger:Cycle average measurement record, with a programmable period, 150000 records maxi on MMC (multi media card) / External driver necessary
|
|
 |
RESISTIVITY / CONDUCTIVITY
BAMOPHOX 322 |
General Catalogue
322-01 |
|
|