| ATEX Products |
 |
| Des têtes bien faites... |
|
|
|
| CP1, Immersion probe for turbidity control |
General Catalogue 425-01 |
CP1

|
|
CP1, Immersion probe for turbidity control
- ON/OFF turbidity control - PVC probe, IP68 - Optical measurement in Infra Red wavelengths - Detection: from 50 to 1300 FAU orfrom 600 to 3000 FAU - Immersion distance of 10 m as a maximum - Fitting and configuration easy with our TRUBOMAT GS3 controller |
A complete system includes a CP1 probe (ZO or ZR type) connected to a TRUBOMAT GS3 controller. It provides a contact signal as soon as the turbidity reaches the preset value. The emitter TT-GS send the IR beam (940 nm pulsated 8 kHz) through the fluid to the receiver TR-GS. The variations due to the turbidity are fully used by the TRUBOMAT to detect the over passing preset value. To avoid false alarms due to air bubbles or accidental excess of turbidity, switching delays are adjustable from 0 to 10 seconds (increasing and decreasing turbidity). |
- Level detection of blanket sludge - phase separation detection - Effluent survey - Survey on turbidity limits
The complete system offers a low cost detection on blanket sludge in any WWTP |
50 to 1300 FAU 600 to 3000 FAU |
|
 |
Immersion probe for turbidity control
CP1 |
General Catalogue
425-01 |
|
|